Technical documentation for ORIMA® snow retention systems supplied by Safe Roof Experts across Canada and the United States. Download product data sheets, installation guides, AutoCAD drawings, CSI specifications, engineering test data, and warranty certificates for standing seam metal roof snow guards. All documents are available without registration and are formatted for North American project submissions under NBCC and ASCE 7.
Quick Downloads
↓ CSI Spec 07 72 53
↓ Installation Guide
↓ Architectural Submittal Package
↓ AutoCAD DWG Package
↓ Declaration of Performance
Product Technical Library
The ORIMA® LE2 is a steel tubular snow retention system for mechanical lock standing seam metal roofs — single lock and double lock profiles. The system uses a non-penetrating seam clamp with no holes drilled in the roof panel. Static load capacity: 5 kN/m for 10 minutes (tested to SS 831367). Material: hot-dip galvanized steel Z275 g/m² with polyester powder coating. Distributed in Canada and the USA by Safe Roof Experts, Toronto, ON.
ORIMA® LE2 Steel Tubular Snow Guard
Mechanical Lock Standing Seam — Single Lock & Double Lock
Full Package Available
Installation Guides by Roof Type
ORIMA® LE2 snow guards are designed for mechanical lock standing seam metal roofs. The bracket clamps onto the seam without penetrating the panel. Maximum bracket spacing is 1,200 mm (48″). First row should be installed directly above the exterior wall line or higher.
| Roof Profile | Compatible System | Attachment | Installation Guide |
|---|---|---|---|
| Standing Seam — Single LockMechanical lock, one fold | ORIMA® LE2 | Non-penetrating seam clamp | PDF ↓ |
| Standing Seam — Double LockMechanical lock, double fold | ORIMA® LE2 | Non-penetrating seam clamp | PDF ↓ |
| Standing Seam — Snap LockClick-lock profile | ORIMA® LE2SL | Non-penetrating seam clamp | Contact us → |
Engineering & Testing
ORIMA® snow retention systems are tested to SS 831367 — Swedish static load standard, comparable to ASTM E330. Declared mechanical strength: 5 kN/m for 10 minutes. There is no harmonized EN standard for snow guards; CE marking does not apply. Snow guard spacing is calculated per NBCC (Canada) and ASCE 7 (USA) based on ground snow load (Ss) and roof pitch.
Load Testing
- Static load: 5 kN/m / 10 min
- Standard: SS 831367 (Sweden)
- Comparable to ASTM E330
- Tested by Orima-Tuote Oy
Corrosion Resistance
- Min. 1,000 hrs salt spray
- Standard: ASTM B117
- Base: Hot-dip galv. Z275 g/m²
- Top: Polyester powder coat
Snow Load Design
- NBCC — Canada (Ss ground load)
- ASCE 7 — USA
- Spacing tables: metric + imperial
- Use Snow Guards Calculator →
Material Standards
- ASTM A653 — Zinc-Coated Steel
- AAMA 2604/2605 — Powder Coat
- CSA S136 — Cold-Formed Steel
- ISO 898 — Fastener class 8.8
Certifications & Compliance
Declaration of Performance
Issued by Orima-Tuote Oy, Finland. Signed by CEO. Mechanical strength: 5 kN/m per SS 831367.
50-Year Material Warranty
Roof safety systems and ladders. Validated in Nordic climate conditions. 30-year finish warranty.
Architect & Specifier Resources
| Resource | Format | Download / Access |
|---|---|---|
| CSI Specification — Section 07 72 53 Snow Guards Division 07 — Thermal and Moisture Protection. 3-Part format with spacing tables, NBCC and ASCE 7 references, LEED data. | PDF ↓ | |
| Architectural Submittal Package — ORIMA® LE2 Product data, technical specs, CAD drawing, standards compliance, approval sign-off block. Ready for submittal log. | PDF ↓ | |
| Snow Guard Layout Calculator Calculate row spacing by roof pitch and ground snow load. Imperial and metric. Export PDF with logo. | Web tool | Open → |
| Project Layout Review Submit roof dimensions, pitch, and location. We provide a project-specific spacing drawing at no charge. | — | Request → |
Need a layout drawing for your project?
Send us roof dimensions, pitch, and city — we calculate the snow guard layout at no charge.